刘武忠, 林永昕, 李克勇, 赵乾魁, 孙原. 室内空调使用不当致2例急性CO中毒事故报告[J]. 职业卫生与应急救援, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029
引用本文: 刘武忠, 林永昕, 李克勇, 赵乾魁, 孙原. 室内空调使用不当致2例急性CO中毒事故报告[J]. 职业卫生与应急救援, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029
LIU Wuzhong, LIN Yongxin, LI Keyong, ZHAO Qiankui, SUN Yuan. Report on two cases of CO poisoning by misuse of indoor air conditioner[J]. Occupational Health and Emergency Rescue, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029
Citation: LIU Wuzhong, LIN Yongxin, LI Keyong, ZHAO Qiankui, SUN Yuan. Report on two cases of CO poisoning by misuse of indoor air conditioner[J]. Occupational Health and Emergency Rescue, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029

室内空调使用不当致2例急性CO中毒事故报告

Report on two cases of CO poisoning by misuse of indoor air conditioner

  • 摘要: 通过调查发生在某公司司机休息室的一起一氧化碳(CO)中毒事故, 发现中毒原因是废气管道布局设计不合理, 直燃型空调锅炉节气阀垫片损坏没有及时更换垫片, 单靠调节流量泵调节燃气流量, 造成燃气、空气比例失调, 导致大量CO产生, 沿废气管道裂缝进入休息室引起CO中毒。有毒气体管道布局设计时要严格遵守相关规定, 维修作业时应严格管理。

     

/

返回文章